Technical data
A43 A44
Voltage/current inputs
Nominal voltage 3 x 230/400 V AC
Voltage range 3 x 57.7/100 ... 288 /500 V AC (-20% - +15%)
Power dissipation voltage circuits 0.8 VA (0.8 W) total
Power dissipation current circuits 0.007 VA (0.007 W) per phase at 230 V
AC and Ib
0.001 VA (0.001 W) per phase at 230 V
AC and Ib
Base current Ib5 A -
Rated current In-1 A
Reference current Iref 5 A -
Transitional current Itr 0.5 A 0.05 A
Maximum current Imax 80 A 6 A
Minimum current Imin 0.25 A 0.01 A
Starting current Ist < 20 mA < 1 mA
Terminal wire area 1 - 25 mm20.5 - 10 mm2
Recommended tightening torque 3 Nm 1.5 Nm
Communication
Terminal wire area 0.5 - 1 mm2
Recommended tightening torque 0.25 Nm
Transformer ratios
Configurable current ratio (VT) -1/999 - 999999/1
Configurable current ratio (CT) -1/9 - 9999/1
Pulse indicator (LED)
Pulse frequency 1000 imp/kWh 5000 imp/kWh
Pulse length 40 ms
General data
Frequency 50 or 60 Hz ± 5%
Accuracy Class B (Cl. 1) or reactive Cl. 2
Active energy 1%
Display of energy Pixel oriented
Environmental
Operating temperature -40°C - +70°C
Storage temperature -40°C - +85°C
Humidity 75% yearly average, 95% on 30 days/year
Resistance to fire and heat Terminal 960 °C, cover 650°C (IEC 60695-2-1)
Resistance to water and dust IP20 on terminal block without protective enclosure and IP51 in protective enclosure,
according to IEC 60529.
Mechanical environment Class M2 in accordance with the Measuring Instrument Directive (MID). (2004/22/EC).
Electromagnetic environment Class E2 in accordance with the Measuring Instrument Directive (MID), (2004/22/EC).
Outputs
Current 2 - 100 mA
Voltage 5 - 40 V DC
Pulse output frequency Programmable: 1 - 999999 imp/kWh
Pulse length Programmable: 10 - 990 ms
Terminal wire area 0.5 - 1 mm2
Recommended tightening torque 0.25 Nm
EMC compatibility
Impulse voltage test 6 kV 1.2/50 μs (IEC 60060-1)
Surge voltage test 4 kV 1.2/50 μs (IEC 61000-4-5)
Fast transient burst test 4 kV (IEC 61000-4-4)
Immunity to electromagnetic HF-fields
80 MHz - 2 GHz at 10 V/m (IEC 61000-4-3)
Immunity to conducted disturbance 150 kHz - 80 MHz (IEC 61000-4-6)
Immunity to disturbance with harmonics 2 kHz - 150 kHz
Radio frequency emission EN 55022, class B (CISPR22)
Electrostatic discharge 15 kV (IEC 61000-4-2)
Standards
IEC 62052-11, IEC 62053-21 class 1 & 2, IEC 62053-23 class 2,
IEC 62054-21,
GB/T 17215.211-2006, GB/T 17215.321-2008 class 1 & 2,
GB 4208-2008, EN 50470-1,
EN 50470-3 category B.
Mechanical
Material Polycarbonate in transparent front glass, bottom case, upper case and terminal cover.
Glass reinforced polycarbonate in polycarbonate in terminal cover.
Dimensions
Width 123 mm
Height 97 mm
Depth 65 mm
DIN modules 7
© Copyright 2014 ABB. All rights reserved.
Specication subject to change without notice.
To get more information,
install QR code reader on
your mobile device, scan
the code and see more.
ABB AB
Meters
Low Voltage Products
Box 1005
S-61129 Nyköping, Sweden
Telephone +46 155 29 50 00
www.abb.com/lowvoltage
Wiring diagram
Dimensions
3 wire connection, 2 elements
3 4 6 7 9
L1
L2
L3
1 12
10
A43
34 6 7 9
L1
L2
L3
N
112
10
4 wire connection, 3 elements
3 wire connection, 2 elements
3 5 7 8 9
L1
L2
L3
1 2 11
P1 P1
P1 P2
S1 S2
3 4 5 6 7 8 9
L1
L2
L3
N
1 2 11
P1 P1 P1
P1 P2
S1 S2
4 wire connection, 3 elements
A44
123
89
93
45
97
43
58
65