FXP7000 AC-DC Series Data Sheet
REV. FEB 12, 2005 Page 2 of 8 www.power-one.com
Output Specifications
PARAMETER DESCRIPTION/CONDITIONS MIN NOM MAX UNITS
Output Voltage An additional 1.0 Volt is provided to the output terminals to provide for 45.6 48 50.4 V
Adjustment Range load lead losses.
Output Power Continuous duty rating. 7000 Watts
Output Current Continuous duty rating. 145 A
Efficiency Full rated load (208Vac). 88 91 %
Regulation Load, Maximum deviation with 0 to 100% load change:
With Remote Sense connected: 0.2
With Remote Sense not connected: 0.75 %
Utilizing Droop Current Share: 2.0
Line, Under all specified operating conditions. 0.2
Ripple & Noise Measured at mating connector w/ 0.01µF + 10µF Tant.
20 MHz BW: 1 % p-p
100 MHz BW: 2
Overshoot / Undershoot Output voltage overshoot/undershoot at turn-on. 0 %
Minimum Loads Minimum loading required to maintain regulation. 0 A
Transient Response Maximum recovery time, to within 1% of initial set Time: 800 µs
point due to a 25% load change, 1A/µS. Deviation: 3.2 %
Turn-On Delay Time required for initial output voltage stabilization after power-up. 3 s
Turn-on Rise Time Time required for output voltage to rise from 10% to 90%. 100 ms
Interface Signals and Protection
PARAMETER (NOTE 1,2) DESCRIPTION/CONDITIONS MIN NOM MAX UNITS
AC Power Fail Warning Warning provided prior to Vout dropping 5% after loss of AC input. 4 ms
Auxiliary Power Output voltage - diode isolated. Inclusive of line, load, and initial tolerances. 11.6 12.0 12.4 V
Output current. 500 mA
Current Monitor Monitor output current over a compliance range of 0~10V.
Normal output: 0.10 mA/A
Total error current: 0.5 0 0.5 mA
Current Share Static sharing deviation as a percent of full-load rating Active: 5 %
for loads >10%. Passive: 10
Input Range Select Status Maximum signal resistance in high input voltage range selection. 0.10 ⍀
Loss of Phase Warning Warning provided prior to protective reduction in current limit. 500 ms
Output Inhibit Voltage required to enable supply (0.1 mA sink). (NOTE 3) 1.0 V
Output Interlock Voltage required to enable supply (6 mA sink). (NOTE 3) 1.0 V
Output Overload Protection Straight line current limit (above approx. 5V Vout). 149 156 A
Output Overload Warning Signal level on overload. 2.2 V
Output Short Circuit Protection Occurs on overload when Vout is below approx. 5V. Iavg: 25 90 A
May operate in burst-mode.
Output Voltage Fault Signal Deviation from adjusted Vout that is considered as a fault. ±3 ±4 ±5 %
Output Voltage Margin Output voltage swing available through Margin pin (analog). ±4.8 ±5.0 ±5.2 %
Overtemperature/ Time between fault warning and shutdown. 100 ms
Fan Failure Warning Latching shutdown.
Overvoltage Protection Latch style overvoltage protection. 55.2 57.6 60.0 V
Power Supply Present Signal Resistance to logic ground upon insertion of supply. 1000 ⍀
Remote Sense Maximum load lead loss compensation (round trip). 1.0 V
NOTES: 1) All logic outputs listed below feature a standard active pull-down output with 0.4V max at 40 mA sink capability, and a 100k pull-up to 5V.
2) In addition to those listed below, signals and front-panel LEDs are provided to indicate: overtemperature/fan fault, AC phase
imbalance, output good, interlock open, and supply inhibited. The FXP also provides 4 LED’s indicating output loading.
3) Both signals must be pulled to logic ground for the unit to operate. Enables are 100% redundant internally for applications where redundant inhibit is desirable.
Contact factory for additional design details.