DATASHEET - ESR5-NO-31-AC-DC
Safety relay emergency stop/protective door, 24V-230VDC/AC, 3 enabling
paths
Part no. ESR5-NO-31-AC-DC
Catalog No. 118704
Eaton Catalog No. ESR5-NO-31-AC-DC
EL-Nummer
(Norway)
4133321
Delivery program
Product range Electronic safety relays
Basic function Emergency stop; emergency switching off
Protective door
Feedback circuit
Features
Mounting width mm 45
Automatic or manual start
Start button monitoring
Operation single-channel
dual-channel
Supply voltage Us 24 V DC
24 V AC, 50/60 Hz
24 V AC/DC - 230 V AC/DC, 50/60 Hz
115 V AC, 50/60 Hz
230 V AC, 50/60 Hz
Approval
Safety related characteristics Cat. 4
PL e according to EN ISO 13849-1
SILCL 3 according to IEC 62061
SIL 3 according to IEC 61508
Number of enabling paths to EN 60204-1 Stop functions
category
Enable current paths to IEC/EN 60204-1 Stop category 0 3
Signal current paths 1
Technical data
General
Intended use Sicherheitsrelais zur Überwachung von Not-Halt- und Schutztürschaltern.
Mit Hilfe dieses Modules werden Stromkreise sicherheitsgerichtet unterbrochen.
Policies List EMV 2004/108/EG, Maschinen 2006/42/EG
Standards EN ISO 13849-1:2008,
EN 62061:2005+AC:2010,
EN 61508, Parts 1-7:2001,
EN 50178:1997,
EN 60204-1:2006+A1:2009
Dimensions (W x H x D) mm 45 x 114.5 x 99
Mounting width mm 45
Weight kg 0,31
Mounting position As required
Mounting Top-hat rail IEC/EN 60715, 35 mm
Connection type M3 screw terminals
Lifespan, mechanical Operations x 10610
Terminal capacity
Solid mm21x (0.2 – 2.5)
2x (0.2 – 1)
Flexible with ferrule mm21x (0.25 – 2.5)
2x (0.25 – 1)
Solid or stranded AWG 24 - 12
Terminal screw Nm
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.6 x 3.5
04/09/2018 Eaton 118704 ED2018 V42.0 EN 1 / 6
Max. tightening torque Nm 0.6
Stripping length mm 7
Material Housing: polyamide PA not reinforced
Contacts: Material: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au)
Duty factor % DF 100
Operating conditions
Climatic environmental conditions
Climatic proofing Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Ambient temperature
Operation ϑ °C -20 - +55
Storage ϑ °C -25 - +85
Condensation Non-condensing
Atmospheric conditions
relative humidity % Max. 75
Air pressure (operation) hPa 795 - 1080
Altitude Above sea
level
m 2000
Power loss P W 4.8
Ambient conditions, mechanical
Degree of protection to VDE 0470-1
Enclosures IP20
Terminals IP20
Degree of Protection Installation location: ≥ IP54
B10d [switching cycles] 300000
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Vibrations (IEC/EN 60068-2-6) 10 - 150 Hz
Amplitude: 0.15 mm
Acceleration: 2 g
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 14-95
Rated impulse withstand voltage Uimp V AC 4000
Insulation Basic isolation
Safe isolation, reinforced isolation, and 6 kV between input circuit and enable
current paths (13-14, 23-24, 33-34) and between (13-14, 23-24, 33-34) with relation to
each other.
Overvoltage category/pollution degree III/2
Stop category according to
EN60204-1
1,26
Technical safety parameters:
Values according to EN ISO 13849-1
Performance level according
to EN ISO
13849-1
PL e
Category according
to EN ISO
13849-1
Kat. 4
Safety integrity level claim limit in accordance
with 62061
SILCL 3
Safety integrity level In
accordance
with IEC 61508
SIL 3
Probability of failure per hour PFHdx 10-10 1.26
Prooftest High Demand Months 240
Prooftest Low Demand Months 59
Rated operational voltage UeV AC 230
Rated operational voltage UeV 24 - 230 V AC, 24 - 230 V DC
Permissible range 0.85 - 1.1 x Ue
Rated insulation voltage UiV AC 250
Quadratic summation current A250 A2 (ITH2 = I12 + I22 + … + IN2)
Inrush current A min - max 0.025 - 6
Minimum switching capacity W 0.4
04/09/2018 Eaton 118704 ED2018 V42.0 EN 2 / 6
Control circuit
Power supply circuit
AC operated 50/60 Hz W 5.8
DC operated W 2.9
Fuse for control circuit supply
24 V short-circuit proof
115 V/230 V short-circuit proof
Input data
Rated current mA S10, S12, S22:35, S34, S35:45
Current consumption mA 120 V AC: 20
230 V AC: 10
24 V DC: 120
Voltage at input, starting and feedback circuit V DC Approx. 24
Max. resistive load of the cable R ≦ 11
Short-circuit current A 0.7
Pick-up time (K1, K2) for UN automatic mode, typical tAms 250
Pick-up time (K1, K2) for UN manual operation, typical tAms 60
Pick-up time ms at Ue in automatic mode: normally 250
at Ue in manual mode: normally 60
Reset time (K1, K2) for UN , normally tRms 20 (when actuated via S11/12 and S21/S22)
500 (on actuation via A1)
50 (at 24 V DC)
110 (at 120 V AC)
280 (at 230 V AC)
Recovery time tWms Approx. 1000
Simultaneity for inputs 1/2 tsync ms
Maximum permissible total cable resistance (input and starting circuits for UN) RLΩ 11
Maximum switching frequency Hz 0.5
Status indication LED Green
Output data
Contact type
Non-delayed enable current paths 3
Delayed signal current path 1
Switching voltage min – max 15 - 250 V AC
15 - 250 V DC
Limiting continuous current A per N/O: 6
N/C: 6
Short-circuit protection for output circuits, external Fuse 6 A gL/gG
Output fuse
NEOZED (N/O) gL/gG 6
NEOZED (N/C) gL/gG 6
Maximum breaking power
Resistive load (τ = 0 ms)
24 V DC W 144
48 V DC W 384
110 V DC W 80
220 V DC W 66
250 V AC VA 2000
Inductive load (τ = 40 ms)
24 V DC W 48
48 V DC W 48
110 V DC W 48
220 V DC W 48
Switching capacity
In accordance with IEC 60947-5-1
AC-15
230 V A 3 A bei 3600S/h
DC-13
24 V A 3 A bei 3600S/h
04/09/2018 Eaton 118704 ED2018 V42.0 EN 3 / 6
Further information (flip catalog) description
Electromagnetic compatibility (EMC)
Emitted interference In accordance with EN 61000-6-4
Interference immunity according to EN 61000-6-2
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation InA 0
Heat dissipation per pole, current-dependent Pvid W 0
Equipment heat dissipation, current-dependent Pvid W 0
Static heat dissipation, non-current-dependent Pvs W 4.8
Heat dissipation capacity Pdiss W 0
Operating ambient temperature max. °C -20
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Meets the product standard's requirements.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility.
10.12 Electromagnetic compatibility Is the panel builder's responsibility.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 6.0
Relays (EG000019) / Device for monitoring of safety-related circuits (EC001449)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Monitoring equipment (low-voltage switch technology) / Device for monitoring of safety-
related circuits (ecl@ss8.1-27-37-18-19 [ACO304008])
Model Basic device
Suitable for monitoring of position switches Yes
Suitable for monitoring of emergency-stop circuits Yes
Suitable for monitoring of valves No
Suitable for monitoring of optoelectronic protection equipment No
Suitable for monitoring of tactile sensors No
Suitable for monitoring of magnetic switches No
Suitable for monitoring of proximity switches No
Type of electric connection Screw connection
Rail mounting possible Yes
Rated control supply voltage Us at AC 50HZ V 0 - 26.4
04/09/2018 Eaton 118704 ED2018 V42.0 EN 4 / 6
Rated control supply voltage Us at AC 60HZ V 0 - 0
Rated control supply voltage Us at DC V 0 - 0
Voltage type for actuating AC/DC
With detachable clamps Yes
Evaluation inputs One- and two-channel
With start input Yes
With muting function No
With feedback circuit Yes
Release-delay s 0 - 0
Number of outputs, safety related, undelayed, with contact 3
Number of outputs, safety related, delayed, with contact 0
Number of outputs, safety related, undelayed, semiconductors 0
Number of outputs, safety related, delayed, semiconductors 0
Number of outputs, signalling function, undelayed, with contact 1
Number of outputs, signalling function, delayed, with contact 0
Number of outputs, signalling function, undelayed, semiconductors 0
Number of outputs, signalling function, delayed, semiconductors 0
Category according to EN 954-1 4
Type of safety acc. IEC 61496-1 -
Stop category acc. to IEC 60204 0
Performance level acc. to EN ISO 13849-1 Level e
SIL according to IEC 61508 3
With approval for TÜV Yes
With approval for BG BIA No
With approval according to UL Yes
Width mm 45
Height mm 99
Depth mm 114.5
Approvals
Product Standards IEC/EN see Technical Data; UL 508; CSA-C22.2 No. 14-95; CE marking
UL File No. E29184
UL Category Control No. NKCR; NKCR7
CSA File No. UL report applies to both US and Canada
CSA Class No. 3211-83; 3211-03
North America Certification UL listed, certified by UL for use in Canada
Degree of Protection IEC: IP20, UL/CSA Type: -
04/09/2018 Eaton 118704 ED2018 V42.0 EN 5 / 6
Dimensions
Assets (Links)
Declaration of Conformity
00002514
Additional product information (links)
IL05013031Z operator manual for electricians
IL05013031Z operator manual for electricians ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL05013031Z2014_04.pdf
description http://de.ecat.moeller.net/flip-cat/?edition=HPLTE&startpage=13.15
04/09/2018 Eaton Industries GmbH
http://www.eaton.eu
© 03/2018 by Eaton Industries GmbH
Eaton 118704 ED2018 V42.0 EN
6 / 6