Features
Three-phase AC input
Suitable for 3U or 5U height mounting
Single-wire current share or Droop current share
Remote voltage adjust and current monitoring
Overtemperature, overload, and overvoltage protection
LED supply status indicators
Current share control for up to 30 units
Standard & customized rack adaptors available
Front panel selectable-input-range model availability
FXP7000
Front and Rear Views
The FXP7000 Series of rack-mounted power systems
provides AC front-end capability to automatic test
equipment, telecom, data communications, and other
distributed power designs. The pluggable FXP supplies
do not include an output isolation diode and may be
paralleled up to 210 kW of total output power. These
supplies provide excellent protection against input
voltage transients.
Access to interfaces for remote sensing, remote voltage
adjust, current sharing, current monitoring, power supply
status, standby voltage and inhibit, as well as power
connections, is through a connector at the rear of the
supply. The FXPhas its fan, handles, volt age adjust, and
indicator lights on the front panel and a single hot-plug
connector on the rear. Airflow is from the front through
the rear. Alarm, monitoring, and control signals are
floating from the main output and can be referenced to
the positive or negative output or sense line of the power
supply. The output is floating with respect to the chassis
and may be used as a positive or negative polarity
supply.
The FXP7000 Series meets international safety
requirements and is CE Marked to the Low Voltage
Directive. This series operates on three-phase European
voltages as well as (up to) 480VAC, delta or wye.
Distributed Power Front-End
FXP7000 AC-DC Series Data Sheet
REV. AUG 15, 2004 Page 1 of 8 www.power-one.com
Hot-Pluggable Model
MODEL OUTPUT INPUT VOLTAGE RANGE ADJUSTMENT MAXIMUM OUTPUT LINE LOAD INITIAL SETTING
VOLTAGE 3-PHASE (VAC) RANGE CURRENT REGULATION REGULATION (NOTE 1) ACCURACY
FXP7000-48 48V 342 to 528 45.6V to 50.4V 145A 0.15% 0.2% 47.90V to 48.10V
FXP7000-48-240 48V 180 to 264 45.6V to 50.4V 145A 0.15% 0.2% 47.90V to 48.10V
FXP7000-48-S 48V 180 to 264 or 342 to 528 45.6V to 50.4V 145A 0.15% 0.2% 47.90V to 48.10V
NOTES: 1) With Remote Sense connected.
Input Specifications
PARAMETER DESCRIPTION/CONDITIONS MIN NOM MAX UNITS
Input Voltage - AC 3-phase delta low input range, nominal. 200 240 VAC
3-phase delta high input range, nominal. 380 480
Continuous deviation from the above nominals. -10 +10 %
Input Current Per phase at full rated load. FXP7000 at 180 VAC: 30 ARMS
Inrush Surge Current Internally limited. Vin = 264VAC (one cycle). 25° C: 38 APK
Vin = 528VAC (one cycle). 25° C: 38
Input Frequency AC input. 50 60 Hz
Hold-up Time After last AC line peak at full power. 208 VAC: 17 ms
400 VAC: 13
Operating Frequency Switching frequency, fixed. 100 kHz
Power Factor 0.90 W/VA
Output Specifications
PARAMETER DESCRIPTION/CONDITIONS MIN NOM MAX UNITS
Output Voltage An additional 1.0 Volt is provided to the output terminals to provide for 45.6 48 50.4 V
Adjustment Range load lead losses.
Output Power Continuous duty rating. 7000 Watts
Output Current Continuous duty rating. 145 A
Efficiency Full rated load (208Vac). 88 91 %
Regulation Load, Maximum deviation with 0 to 100% load change:
With Remote Sense connected: 0.2
With Remote Sense not connected: 0.75 %
Utilizing Droop Current Share: 2.0
Line, Under all specified operating conditions. 0.2
Ripple & Noise Measured at mating connector w/ 0.01µF + 10µF Tant.
20 MHz BW: 1 % p-p
100 MHz BW: 2
Overshoot / Undershoot Output voltage overshoot/undershoot at turn-on. 0 %
Minimum Loads Minimum loading required to maintain regulation. 0 A
Transient Response Maximum recovery time, to within 1% of initial set Time: 800 µs
point due to a 25% load change, 1A/µS. Deviation: 3.2 %
Turn-On Delay Time required for initial output voltage stabilization after power-up. 3 s
Turn-on Rise Time Time required for output voltage to rise from 10% to 90%. 100 ms
Interface Signals and Protection
PARAMETER (NOTE 1,2) DESCRIPTION/CONDITIONS MIN NOM MAX UNITS
AC Power Fail Warning Warning provided prior to Vout dropping 5% after loss of AC input. 4 ms
Auxiliary Power Output voltage - diode isolated. Inclusive of line, load, and initial tolerances. 11.6 12.0 12.4 V
Output current. 500 mA
Current Monitor Monitor output current over a compliance range of 0~10V.
Normal output: 0.10 mA/A
Total error current: 0.5 0 0.5 mA
Current Share Static sharing deviation as a percent of full-load rating Active: 5 %
for loads >10%. Passive: 10
Input Range Select Status Maximum signal resistance in high input voltage range selection. 0.10
Loss of Phase Warning Warning provided prior to protective reduction in current limit. 500 ms
Output Inhibit Voltage required to enable supply (0.1 mA sink). (NOTE 3) 1.0 V
Output Interlock Voltage required to enable supply (6 mA sink). (NOTE 3) 1.0 V
Output Overload Protection Straight line current limit (above approx. 5V Vout). 149 156 A
Output Overload Warning Signal level on overload. 2.2 V
Output Short Circuit Protection Occurs on overload when Vout is below approx. 5V. Iavg: 25 90 A
May operate in burst-mode.
Output Voltage Fault Signal Deviation from adjusted Vout that is considered as a fault. ±3 ±4 ±5 %
Output Voltage Margin Output voltage swing available through Margin pin (analog). ±4.8 ±5.0 ±5.2 %
Overtemperature/ Time between fault warning and shutdown. 100 ms
Fan Failure Warning Latching shutdown.
Overvoltage Protection Latch style overvoltage protection. 55.2 57.6 60.0 V
Power Supply Present Signal Resistance to logic ground upon insertion of supply. 1000
Remote Sense Maximum load lead loss compensation (round trip). 1.0 V
NOTES: 1) All logic outputs listed below feature a standard active pull-down output with 0.4V max at 40 mA sink capability, and a 100k pull-up to 5V.
2) In addition to those listed below, signals and front-panel LEDs are provided to indicate: overtemperature/fan fault, AC phase
imbalance, output good, interlock open, and supply inhibited. The FXP also provides 4 LED’s indicating output loading.
3) Both signals must be pulled to logic ground for the unit to operate. Enables are 100% redundant internally for applications where redundant inhibit is desirable.
Contact factory for additional design details.
FXP7000 AC-DC Series Data Sheet
REV. AUG 15, 2004 Page 2 of 8 www.power-one.com
Safety, Regulatory, and EMI Specifications
PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS
Agency Approvals UL60950/CSA60950-00 (cULus), IEC60950, EN60950 (TÜV),
CE marked for the Low Voltage Directive
Electromagnetic Interference FCC CFR title 47 Part 15 Sub-Part B - Conducted. A
EN55022 / CISPR 22 Conducted. A Class
ESD Susceptibility Per EN61000-4-2, level 4. 8 kV
Radiated Susceptibility Per EN61000-4-3, level 3. 10 V/M
EFT/Burst Per EN61000-4-4, level 4. ±4 kV
Input Transient Protection Per EN61000-4-5, Class 4. Line-to-Line: 4 kV
Line-to-Ground: 2 (4kV Pending)
Voltage Sag Immunity Per SEMI F47-0200 FXC/FXP7000 Pending
Leakage Current Per UL60950 and FXP7000 at 240 VAC, 60 Hz: 5
EN60950: FXP7000 at 400 VAC, 50 Hz: 7 mA
FXP7000 at 480 VAC, 60 Hz: 10
Environmental Specifications
PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS
Altitude Operating. 10k ASL Ft.
Non-Operating. 40k
Operating Temperature At 100% load: 0 40 °C
At 50% load: 70
Storage Temperature -40 85 °C
Temperature Coefficient 0°C to 70°C (after 15-minute warm-up). .02 %/°C
Relative Humidity Non-Condensing. 95 %RH
Shock Operating: half-sine 10 ms, 3 axis +20 GPK
Non-operating: half-sine 10 ms, 3 axis +40
Vibration Operating: swept sine 5-2000-5 Hz, 5-32 Hz, 0.02îDA, 32-2000 Hz 1 GPK
Non-operating: random 10-2000 Hz 6.15 Grms
Airflow Airflow provided through the supply from front to rear. 155 cfm
4.4 m3/min
555 lfm
2.8 m/s
Weight 29 lb
13 kg
FXP7000 AC-DC Series Data Sheet
REV. AUG 15, 2004 Page 3 of 8 www.power-one.com
BOTTOM VIEW
SIDE VIEW
AAAA
AAAA
AA AA
AAAA
<--AIRFLOW
LOCK HANDLE
16.09"
(408.7mm)
14.259"
(362.18mm)
5.750"
(146.05mm)
1.100"
(27.94mm)
0.480"
(12.19mm) 16.96"
(430.8mm)
1.759"
(44.68mm)
4.000"
(101.6mm)
15.462"
(392.73mm)
4.954"
(125.83mm)
0.87"
(22.1mm)
8.00"
(203.2mm)
0.204"
(5.18mm)
0.649"
(16.48mm)
0.590"
(14.99mm)
0.341"
(8.66mm)
7.509"
(190.73mm)
11.704"
(297.28mm)
LED HANDLE
LOCK HOOK
NOTE:
TOTAL BOTTOM STACKUP OF
RACK MUST BE NO GREATER
THAN 0.204".
FOR OPTIONAL HARD MOUNTING, USE
M4 X 0.7 SCREWS, 8PL (MARKED A) ON
SIDE OR BOTTOM WITH MAXIMUM
PENETRATION 3.8mm.
RECOMMENDED MOUNTING TORQUE
10.5 INCH LBS. (0.64N/M)
REAR VIEW
2.437"
(61.90mm)
3.901"
(99.09mm)
0.521"
(13.24mm)
FRONT VIEW
5.000"
(127mm)
0.222"
(5.64mm)
0.090"
(2.29mm)
2PL 4.552"
(115.62mm)
0.226"
(5.74mm)
CONNECTOR MATES WITH
ELCON HOUSING PART NUMBER
296-22-01100
LOCK HANDLE
RELEASE
CENTER
-TO-
CENTER
INPUT VOLTAGE
DISPLAY CUTOUT
C
LC
L
MAINTAIN 25 SQ IN MIN
FREE AREA (FRONT AND
REAR) FOR AIR COOLING
480VAC
INPUT VOLTAGE RANGE
SELECT MODULE
ROTATE 180 DEGREES FOR 240 VAC
WHEN USING THE
FXP7000-48-S MODEL
INPUT VOLTAGE LABEL
HERE FOR FXP7000-48
OR FXP7000-48-240
FXP7000 OVERALL SIZE: 16.96" x 8.00" x 5.00" (430.8mm x 203.2mm x 127.0mm)
FXP7000 AC-DC Series Data Sheet
REV. AUG 15, 2004 Page 4 of 8 www.power-one.com
0.129" 4PL
(3.28mm)
1.484" 2PL
(37.69mm)
19.000"
(482.6mm)
5.215"
(132.46mm)
2.250" 2PL
(57.15mm)
18.312"
(465.12mm)
FXP7000 2PL
FRH7000 POWER SHELF, FRONT VIEW
NOTE:
FXP7000 POWER SUPPLIES ARE SHOWN FOR ILLUSTRATION PURPOSES
ONLY AND ARE NOT INCLUDED AS PART OF POWER SHELF ASSEMBLY.
480VAC
480VAC
J2 AC INPUTS J3
3 PHASE 3 WIRE + PE
J1
-+
12
3
FRH7000 POWER SHELF, REAR VIEW
0.000
0.000
UNIT
LABEL
0.61"
(15.5mm)
3.56"
(90.4mm)
5.215"
(132.46mm)
2.74"
(69.6mm)
4.38"
(111.25mm)
9.42"
(239.27mm)
15.14"
(384.56mm)
16.84"
(427.74mm)
17.14"
(435.34mm)
19.000"
(482.6mm)
0.66"
(16.76mm)
1.86"
(47.24mm)
10/32 GROUND
STUD 2PL
AMP PN 213581-1
WITH SILVER-PLATED
CONTACTS
15.44"
(384.56mm)
PIN 1
5/16-18 STUD 2 PL
ACCOMODATES RING
LUG 1.08 MAX WIDTH
2 PL
2 PL
2 PL
NOTES:
1. FOR CLARITY, FINGER GUARD FOR DC OUTPUT
TERMINALS IS NOT SHOWN IN THIS ILLUSTRATION.
50-PIN SIGNAL HEADER
WITH KEYING AND LATCHES
(AMP PN: 1-499141-0)
ATTACH EARTH GNDS BEFORE AC CONNECTORS
®
Note: The FRH7000 Power Shelf is designed for alternative vertical mounting with the right side down.
FXP7000 AC-DC Series Data Sheet
REV. AUG 15, 2004 Page 5 of 8 www.power-one.com
FILLER PANEL KIT, PN: 088-101378
(Used with FRH7000 Power Shelf)
This kit is used to cover an unused right-side slot of the FRH7000 Power Shelf (as viewed from the front of the FRH7000). The kit can be installed before, or after
installation of the power shelf into the rack.
FRH7000 POWER SHELF, RIGHT-SIDE VIEW
21.91"
(556.5mm)
24.000"
(609.6mm)
4.000"
(101.6mm)
0.715"
(18.16mm)
1/4-20 INSERTS 2 PL
EACH SIDE FOR
REAR SUPPORT
CUSTOMER-SUPPLIED
CABLES OR BUS BARS
RACK MOUNTING FLANGE
BRACKET, 2 PLACES
FILLER PANEL
(FILLER PANEL KIT AS SEEN FROM INSIDE OF POWER SHELF)
FXP7000 AC-DC Series Data Sheet
REV. AUG 15, 2004 Page 6 of 8 www.power-one.com
- DC OUT +
- DC OUT +
12
1 2
3
5/16-18 STUD 2PL
ACCOMODATES CABLE
LUG 1.08" WIDTH MAX.
50-PIN SIGNAL HEADER
WITH KEYING AND LATCHES
(
AMP PN: 1-499141-0
)
PIN 1
J2 AC INPUTS J3
3 PHASE 3W + PE
10/32 PE STUD 3P
L
AMP PN: 213581-1
WITH SILVER-PLATED
PIN CONTACTS
J1
J4
3.55"
(90.17mm)
1.01"
(25.65mm)
0.40"
(10.16mm)
3.31"
(84.07mm)
4.95"
(125.73mm)
9.42"
(239.27mm)
13.37"
(339.60mm) 13.67"
(347.22mm)
15.07"
(382.78mm) 15.37"
(390.40mm)
16.77"
(425.96mm) 17.07"
(433.58mm)
2.71" 3PL
(68.8mm)
1.07" 3PL
(27.2mm)
0.000
0.000
UNIT
LABEL
FRV7000 POWER SHELF, REAR VIEW
NOTES:
1. FOR CLARITY, FINGER GUARD FOR DC OUTPUT
TERMINALS IS NOT SHOWN IN THIS ILLUSTRATION.
ATTACH EARTH GNDS BEFORE AC CONNECTORS
NOT TO SCALE
18.656" 2PL
(473.86mm)
0.344" 2PL
(8.74mm)
0.000
19.000"
(482.6mm)
8.70"
(221.0mm)
7.184" 2PL
(182.47mm)
1.434" 2PL
(36.42mm)
R 0.129" 4PL
(3.28mm)
0.000
FRV7000 POWER SHELF, FRONT VIEW
NOTE:
FXP7000 POWER SUPPLIES ARE SHOWN FOR ILLUSTRATION PURPOSES
ONLY AND ARE NOT INCLUDED AS PART OF POWER SHELF ASSEMBLY.
NOT TO SCALE
INPUT VOLTAGE RANGE
SELECT MODULE
INPUT VOLTAGE
DISPLAY CUTOUT
480VAC 480VAC 480VAC
®
FXP7000 AC-DC Series Data Sheet
REV. AUG 15, 2004 Page 7 of 8 www.power-one.com
FILLER PANEL KIT, PN: 088-101348
(Used with FRV7000 Power Shelf)
This kit is used to cover an unused left or center slot of the FRV7000 Power Shelf (as viewed from the front of the FRV7000). One kit is required per slot. Kits
can be installed before, or after installation of the power shelf into the rack.
FRV7000 POWER SHELF, LEFT-SIDE VIEW
25.56"
(649.2mm)
0.000
7.20"
(182.9mm)
1.20"
(30.5mm)
0.40"
(10.2mm)
0.214"
(5.44mm)
0.000
COOLING AIR
EXHAUST
COOLING AIR
INTAKE
CUSTOMER-SUPPLIED
DC CABLES
POWER SUPPLY LOCK
HOOK; CLEARANCE
REQUIRED 6 PLACES
FINGER GUARD
FOR DC OUTPUT
TERMINALS
24.00"
(609.6mm)
22.50" 2PL
(571.5mm)
1/4-20 THREADED INSERTS 2PL
EACH SIDE FOR REAR SUPPORT
OF UNIT. DO NOT EXCEED 0.500"
PENETRATION OF SCREW INTO UNIT.
(FILLER PANEL KIT AS SEEN FROM INSIDE OF POWER SHELF)
FILLER PANEL
UPPER BRACKET
LOWER BRACKET
FXP7000 AC-DC Series Data Sheet
REV. AUG 15, 2004 Page 8 of 8 www.power-one.com
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not authorized for use as critical components in life support
systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the
respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change
depending on the date manufactured. Specifications are subject to change without notice.