Features
• Three-phase AC input
• Suitable for 3U or 5U height mounting
• Single-wire current share or Droop current share
• Remote voltage adjust and current monitoring
• Overtemperature, overload, and overvoltage protection
• LED supply status indicators
• Current share control for up to 30 units
• Standard & customized rack adaptors available
• Front panel selectable-input-range model availability
FXP7000
Front and Rear Views
The FXP7000 Series of rack-mounted power systems
provides AC front-end capability to automatic test
equipment, telecom, data communications, and other
distributed power designs. The pluggable FXP supplies
do not include an output isolation diode and may be
paralleled up to 210 kW of total output power. These
supplies provide excellent protection against input
voltage transients.
Access to interfaces for remote sensing, remote voltage
adjust, current sharing, current monitoring, power supply
status, standby voltage and inhibit, as well as power
connections, is through a connector at the rear of the
supply. The FXPhas its fan, handles, volt age adjust, and
indicator lights on the front panel and a single hot-plug
connector on the rear. Airflow is from the front through
the rear. Alarm, monitoring, and control signals are
floating from the main output and can be referenced to
the positive or negative output or sense line of the power
supply. The output is floating with respect to the chassis
and may be used as a positive or negative polarity
supply.
The FXP7000 Series meets international safety
requirements and is CE Marked to the Low Voltage
Directive. This series operates on three-phase European
voltages as well as (up to) 480VAC, delta or wye.
Distributed Power Front-End
FXP7000 AC-DC Series Data Sheet
REV. AUG 15, 2004 Page 1 of 8 www.power-one.com
Hot-Pluggable Model
MODEL OUTPUT INPUT VOLTAGE RANGE ADJUSTMENT MAXIMUM OUTPUT LINE LOAD INITIAL SETTING
VOLTAGE 3-PHASE (VAC) RANGE CURRENT REGULATION REGULATION (NOTE 1) ACCURACY
FXP7000-48 48V 342 to 528 45.6V to 50.4V 145A 0.15% 0.2% 47.90V to 48.10V
FXP7000-48-240 48V 180 to 264 45.6V to 50.4V 145A 0.15% 0.2% 47.90V to 48.10V
FXP7000-48-S 48V 180 to 264 or 342 to 528 45.6V to 50.4V 145A 0.15% 0.2% 47.90V to 48.10V
NOTES: 1) With Remote Sense connected.
Input Specifications
PARAMETER DESCRIPTION/CONDITIONS MIN NOM MAX UNITS
Input Voltage - AC 3-phase delta low input range, nominal. 200 240 VAC
3-phase delta high input range, nominal. 380 480
Continuous deviation from the above nominals. -10 +10 %
Input Current Per phase at full rated load. FXP7000 at 180 VAC: 30 ARMS
Inrush Surge Current Internally limited. Vin = 264VAC (one cycle). 25° C: 38 APK
Vin = 528VAC (one cycle). 25° C: 38
Input Frequency AC input. 50 60 Hz
Hold-up Time After last AC line peak at full power. 208 VAC: 17 ms
400 VAC: 13
Operating Frequency Switching frequency, fixed. 100 kHz
Power Factor 0.90 W/VA