1
Digital Timer H5CN
Miniature DIN-sized (48 x 48 mm) Quartz
Timer with Abundant Series Versions
Series version cover a wide range of rated times;
9.999 s, 99.99 s, 999.9 s, 99 min 59 s, and 99 hrs
59 min.
Selection of elapsed time indication, remaining
time indication, contact output, and solid-state
output types to suit requirements.
Power supply freely selectable within a range of
100 to 240 VAC, as well as 12 to 48 VDC
Models with a memory backup function against
power failure available. RC
Ordering Information
Operating
system
T
ime-limit operation, integrating operation
Resetting system
Power-OFF resetting, external resetting
Control output
Contact output (SPDT)
Solid-state output (open collector)
Digital display (7-segment LEDs)
Not provided
(with IN and UP
indicators)
Provided (with UP indicator)
Not provided
(with IN and UP
indicators)
Provided
(without UP
indicator)
indicators)
UP display timer (increments from 0
to the set time)
DOWN display
timer (decrements
from the set time
to 0)
indicators)
Provided UP
display timer
Backup power supply function
for memory protection
Not provided Not provided
Provided
Not provided Not provided Not provided
Rated
ti
0.001 to 9.999 s
--- --- --- --- H5CN-ZNS H5CN-XZNS
Rated
time
0.001 to 99.99 s
H5CN-AN H5CN-XAN H5CN-XANM H5CN-YAN H5CN-ANS H5CN-XANS
0.1 to 999.9 s
H5CN-BN H5CN-XBN H5CN-XBNM H5CN-YBN --- ---
1 s to 99 min 59 s
H5CN-CN H5CN-XCN H5CN-XCNM H5CN-YCN --- ---
1 min to 99 hrs 59 min
H5CN-DN H5CN-XDN H5CN-XDNM H5CN-YDN --- ---
Note: H5CN
Timer is not supplied with a connecting socket.
Accessories (Order Separately)
Applicable
timer
T
rack mounting socket (see note)
Back connecting socket
Screw terminal
H5CN-jj P2CF-08 P3G-08
H5CN-jjM P2CF-11 P3GA-11
Note: 1. T
rack mounted socket can be used as a front connecting socket.
2.
Specify the desired connecting socket when ordering.
H5CN H5CN
2
Specifications
Ratings
Item Contact output
Solid-state output
Supply voltage
100 to 240 V
AC (50/60 Hz), 12 to 48 VDC
(permissible ripple: 20% max.) (see note) 12 to 48 VDC (permissible ripple: 20% max.)
Operating voltage range
85% to 1
10% of rated supply voltage
Power consumption
Approx. 12 V
A (at 240 V
AC, 50 Hz),
approx. 2.5 W (at 48 VDC)
Approx. 2.5 W (at 48 VDC)
Resetting system and
gate input
Reset by power-OFF (not provided for models with backup power for memory protection):
min. power OFF time: 0.5 s
External reset or gate (common to contact and solid-state inputs): min. reset input signal width: 0.02 s;
residual voltage: 2 V max.
Control outputs SPDT
: 3 A at 250 V
AC, resistive load (cosφ
= 1)
Open collector: 100 mA max. at 30 VDC max.
Note:
Models with memory backup function are not available for this range of DC supply voltages.
Characteristics
Accuracy
of operating time
±
0.01%
±
0.05 s max. (see note 1),
±
0.005%
±
0.03 s max. (see note 2) (see note 3)
Setting error
Influence of voltage
Influence of temperature
Insulation resistance
100 M
min. (at 500 VDC) (between current-carrying terminal and exposed non-current
carrying metal parts, between power supply circuit and control output circuit)
Dielectric strength
2,000 V
AC, 50/60 Hz for 1 min (between current-carrying terminal and exposed
non-current-carrying metal parts, between power supply circuit and control output circuit)
V
ibration resistance
Destruction:
10 to 55 Hz with 0.75-mm double amplitude
Malfunction:
10 to 55 Hz with 0.5-mm double amplitude
Shock resistance
Destruction:
300 m/s
2
(approx. 30G)
Malfunction:
100 m/s
2
(approx. 10G)
Ambient temperature
Operating: –10°
C to 55
°C
Storage: –25°
C to 65
°C
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical:
10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
100,000 operations min. (3 A at 250 V
AC, resistive load)
Approved standards
UL (File No. E41515), CSA (File No. LR22310)
Weight
Approx. 150 g
Note: 1.
When timer operation is started by power application.
2.
When timer operation is started after a reset input has been applied.
3. These
values represent the total accuracy of the timer including the repeat accuracy
, setting error
, and variation due to voltage and
temperature
changes. Note that they also comprise errors due to the rise time of the power source and the operating times of the
internal
and output circuits.
H5CN H5CN
3
Engineering Data
Switching operations (x 10 )
3
Load current (A)
Switching operations (x 10 )
3
Load current (A)
Reference:
A maximum current of 0.15 A can be switched at 125 VDC (cos
φ
= 1). Maximum current of 0.1 A can
be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Operation
Timing Chart
Digital Display
UP Display DOWN Display
Note: For
the models without digital display
,
an IN indicator (LED) is provided to indicate power application. (This LED, however
, goes of
f
when
the reset input is applied.)
H5CN H5CN
4
Dimensions
Note:
All units are in millimeters unless otherwise indicated.
10.9 97.6
44.8 x 44.8
4
48
48 72.5 13.5
0.7
6
8
H5CN-jN, -XjN, -YjN, -jNS, -XjNS
H5CN-XjNM 4
48
48
97.6
72.5
10.9 13.5
44.8 x 44.8
0.7
6
8
H5CN H5CN
5
Accessories (Order Separately)
Track Mounted Socket
P2CF-08
Two, 4.5 dia.
holes
Two, 4.5 dia. holes or M4
Eight, M3.5 x 7.5 Terminal
Arrangement
(Top
V
iew)
Mounting Holes
Mounting Height of
T
imer with Socket
P2CF-08
P2CF-11
Terminal
Arrangement
(T
op V
iew)
Mounting Holes
Mounting Height of
T
imer with Socket
Two, 4.5 dia.
holes
Two, 4.5 dia. holes or M4
Eight, M3.5 x 7.5
sems screw
Note: Track mounting is
also
possible.
Back Connecting Socket
P3G-08
Terminal
Arrangement
(Bottom View)
Mounting Depth of
T
imer with Socket
116.9
95.110.9
H5CN H5CN
6
P3GA-11 T
erminal Arrangement
(Bottom View)
Mounting Track
PFP-100N/PFP-50N (see note) (for PF085A)
(see
note 2)
Note: 1. Meets
DIN EN50 022
2.
This dimension applied to PFP-50F
.
End Plate
PFP-M
Adapter for Flush Mounting
Y92F-30 Panel Cutout
The standard panel cutout
is as below
. (Panel cutout
conforms to DIN 43700.)
Note: 1.
Panel thickness: 1 to 5 mm
2. When gang-mounting the Unit, the orientation of
the Adapter must be changed depending on
whether Units are mounted horizontally or verti-
cally.
3. No cover:
N = (48n – 2.5)
+1/–0
With hard cover:
N
= {48n – 2.5 + (n – 1) x 3}
+1/–0
Spacer
PFP-S
Gang-mounting
of more
than 2 units (horizontally)
27 dia.
Eleven, M3.5
sems
N
58
58
48
48
95.1
10.9
100.2
10.9
Panel For flush mounting
Y92F-30 adapter Back connecting
socket P3G-08
Panel For flush mounting
Y92F-30 adapter Back connecting
socket P3GA-11
H5CN-jN, -XjN, -YjN, -jNS, -XjNS
H5CN-XjNM
H5CN H5CN
7
Protective Cover
The
protective cover shields the front panel, particularly the count value setting section from
dust, dirt, and water drip, as well as prevents malfunctioning of the timer due to static electricity
.
Y92A-48D
(see note 1)
(Soft cover)
Y92A-48B
(see note 2)
(Hard cover)
Note: 1. The soft protective cover allows the set value to be set by depressing the thumbwheel
switches
through it.
2. The
hard protective cover prevents the set value from being altered due to accidental contact
with
the push type thumbwheel switch.
It
may be, however
, dif
ficult to make setting changes of the T
imer with the Y92A-48B Protec
-
tive
Cover attached, which must
be taken into consideration before using the Y92A-48B Pro
-
tective Cover.
Backup Battery
Y92S-20 Connection
of Battery Leads
With socket
P2CF-11
With socket
P3G-11
T
erminal No. 1
T
erminal No. 4
T
erminal No. 1
T
erminal No. 4
H5CN H5CN
8
Installation
Connections
Power Supply Connection
Model
W
ithout Backup Power for Memory Protection
Connect
the timer so that the required supply voltage can be applied
across
terminals
B
and
G.
Model W
ith Backup Power for Memory Protection
Connect
the timer so that the required supply voltage can be applied
across
terminals
B
and
J.
Note: Common
terminal
A
will be internally connected to terminal
B
if the Counter is a model that operates with DC.
Connection of Load Circuit (Control Output)
Model
W
ith Backup Power for Memory Protection
Contact Output Type (H5CN-jN)
Terminals
E
,
F
, and
H
are for contact output contacts. Load 1 con
-
nected in series with NO contact (between terminals F and H) is
normally
open, and the load circuit voltage will be applied after the
lapse
of the set time. The load circuit voltage is
normally applied to
load
B
connected in series with NC contact (between terminals
E
and
H
), which will be open after the lapse of the set time.
Load circuit
voltage
(250 VAC
max.)
Solid-state Output Type (H5CN-jNS)
With H5CN-jNS, a solid-state output is generated by using an
open
collector transistor
. Connect terminal
F
(collector) of the
timer
to
the positive terminal of a load and terminal
H
(emitter) to the neg
-
ative
terminal.
When
connecting
an inductive load to the timer
, connect terminal
E
of
the
timer to the positive terminal of the loads, since a diode is in
-
ternally
connected between terminals
F
and
E.
Model W
ith Backup Power for Memory Protection
Contact Output Type
(Internal circuit of control output contact)
T
erminal
H
,
I
, and
K
are for control output contacts.
(Connection of load circuit)
Load
1 connected in series with
NO contact (between terminals
I
and
K
) is normally open, and the load circuit voltage will be applied
to
it after the lapse of the set time. The load circuit voltage is normally
applied
to load
B
connected in series with NC contact (between ter
-
minals
H
and
K
), which will
be open after the lapse of the set time.
Note: The
maximum load current is 3 A (resistive load).
H5CN H5CN
9
Connection of Reset Input
Model
W
ithout Backup Power for Memory Protection
Connection
of the reset
input contact or an open collector transistor
between
terminals
A
and
C
permits the timer to reset when contact
is made or the transistor turns ON. Use of a high-reliability gold-
plated
contact is recommended for the reset input. For
the reset in
-
put transistor, select the one satisfying the following electrical rat-
ings:
VCEO
= 20 V min.
IC = 50 mA min.
ICBO
= 0.5
µ
A max.
Reset input
contact
(Timer resets
when contact
is made.)
Reset input
transistor
(Timer resets
when transis-
tor is ON.)
Model
W
ith Backup Power for Memory Protection
Connection
of the reset
input contact or an open collector transistor
between
terminals
C
and
G
permits the timer to reset when contact
is made or the transistor turns ON. Use of a high-reliability gold-
plated
contact is recommended for the reset input. For
the reset in
-
put transistor, select the one satisfying the following electrical rat-
ings:
VCEO
= 20 V min.
IC = 50 mA min.
ICBO
= 0.5
µ
A max.
Reset input
contact
(Timer resets
when contact
is made.)
Reset input
transistor
(Timer resets
when transis-
tor is ON.)
Connection of Gate Input
Model
W
ithout Backup Power for Memory Protection
Connection
of the gate
input contact or an open collector transistor
between
terminals
A
and
C
permits the timer to reset when contact
is made or the transistor turns ON. Use of a high-reliability gold-
plated
contact is recommended for the gate input. For the reset in
-
put transistor, select the one satisfying the following electrical rat-
ings:
Gate input contact
(Timer stops when
contact is made.)
Gate input transistor
(Timer stops when
transistor is ON.)
Model
W
ith Backup Power for Memory Protection
Connection
of the gate
input contact or an open collector transistor
between
terminals
C
and
E
permits the timer operation to be inter
-
rupted
while the contact or transistor is in the ON state. The same
recommendations
as mentioned above apply on the use of the gate
input contact or transistor. Use a gate input contact with a short
bounce time because the contact bounce time causes an error in
the
operate time of the timer for a period equalling the bounce time.
Gate input contact
(Timer stops when
contact is made.)
Gate input transistor
(Timer stops when
transistor is ON.)
Simultaneous Input to a Number of H5CN Tim-
ers with the Same Contact
With
one contact, a reset or gate input may be applied to
two or more
H5CN
T
imers as shown below
.
Model W
ithout Backup Power for Memory Protection
Model W
ith Backup Power for Memory Protection
Battery Connection
Connect
the Y92S-20 backup battery between terminals
A
and
D,
paying
attention to the polarities.
H5CN H5CN
10
Battery Connections When Recording Interrup-
tions
Always
connect a battery when using Units with a power interruption
recording function. Any 3-V battery may be used, but the time the
interruption
is recorded for will depend on the capacity
of the battery
.
When using the Unit for the first time after purchase, apply power
and
reset the Unit once before using it. When power is applied for
the
first time, outputs may be produced, so do not connect the out
-
put
terminals.
If
a power interruption continues for
10 minutes or more when a bat
-
tery
is not connected, the display may flash,
the count value and dis
-
plays may be meaningless, and outputs may be produced unpre-
dictably even if the power supply recovers. If this happens, apply
power
to the reset input before using the Unit further
.
When connecting the battery using a Socket (P2CF-11 or
P3GA-11),
check the
terminal numbers on the Socket and connect
the
positive side of the battery to terminal 4 and the
negative side to
terminal
1.
Note:1.
High-speed Repeat Operation Circuit
When
resetting the timer using the reset input terminal, high-speed resetting is possible at a
speed of 0.02 s. Accordingly
, by using
two H5CN T
imers, a high-speed repeat operation circuit can be created.
H5CN
No.
1
H5CN
No. 2
2. Integrating Operation
Use of the gate input terminal permits the timer to sum up timers T
1
, T
2
, and T
3
(i.e., integrating operation) as shown below
.
UP
Display T
imer
DOWN Display T
imer
Operating Time Measurement
The
UP display timers with digital display can be used to measure
the
operating time of other timers or equipment. (For this measure
-
ment,
set the set time to the maximum.)
Note: The
digital display of H5CN stops
incrementing
when
the predetermined operating time of timer
“T”
has elapsed.
H5CN H5CN
11
Alarm Output Circuit
The
illustration shows an example of alarm output circuit. In this
cir
-
cuit,
H5CN outputs an alarm when
the time control by the other timer
is
not completed within the set time of the former
.
Precautions
Setting of Operating Time
Time
Setting Range
Setting range
Rated time
0.001 to 9.999 s
H5CN-jZj
0.001 to 99.99 s
H5CN-jAj
0.1 to 999.9 s
H5CN-jBj
1 s to 99 min 59 s
H5CN-jCj
1 min to 99 hrs 59 min
H5CN-jDj
1. Since
the H5CN T
imer is capable of reading the input data at
any time during normal operation, the set time can be
changed
during power application. This feature sets back the
output from the
timer
by temporarily setting the longer time or
quickens
the output by setting the shorter time. During normal
operation, the set time may be accidentally changed by
touching
a
thumbwheel switch. T
o prevent this possibility
, use
the
optional protective cover Y92A-48B.
2. When
the set time is all zeroes (e.g., 000.0 s or 00 hrs 00 min),
there will be a momentary control output upon power
application
which can be used to check normal output. When
changing the set time during normal operation, pay special
attention
not to alter the set value to this state.
3. When
changing the set time while power is being supplied, an
inadequate
push of the thumbwheel switches will display two
numbers in one digital display window
, causing the operating
time to drift widely. Therefore, press the thumb-wheel
switches surely. Take particular care in the case when the
other
three digits are all zero, since the improper setting of the
fourth switch to create four zeroes will cause a momentary
output.
Undesirable
Setting
(Possible operating time)
5
min 30 s
00 hrs 00 min
(Momentary
output)
4. Take
particular
care with the H5CN-
jZjj
, which is capable
of setting in 1/1000th of a second, since its digital display may
display
an
error of plus or minus 1/1000 s from the set value.
Battery Connection
Even
if the unit is not provided with a backup battery
, the count value
will
be retained for a minimum of 10 min. If a backup battery is con
-
nected,
the count value will
be retained for approx. 5 years. Replace
the
backup battery as quickly as possible within 10 min.
H5CN H5CN
12
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To
convert millimeters into inches, multiply by 0.03937. T
o convert grams into ounces, multiply by 0.03527.
Cat. No. L052-E1-9B In the interest of product improvement, specifications are subject to change without notice.